When through panel mounting a drive, does the power loss in the front of the drive vary with load?
- The loss from the front of the drive is dominated by static losses. Generally, variations in load do not impact the losses in the front of the drive.
Is there a difference in losses between a Master and Follower Pod?
- The Master Control Module has the addition of the Control PCB (including I/O, Encoder, and comms options).
- The Master Control Module may be fitted with option modules. Together, these differences account for approximately 10W
What are the Power Losses when through Panel Mounting the Unidrive M?
|
Frame Size |
Power Loss |
|
3 |
≤ 50 W |
|
4 |
≤ 75 W |
|
5 |
≤ 100 W |
|
6 |
≤ 100 W |
|
7 |
≤ 204 W |
|
8 |
≤ 347 W |
|
9 |
≤ 480 W |
|
10 |
≤ 480 W |
|
11 |
≤ 480 W |
|
Rectifier (all models) |
≤ 50 W |