Supply Requirements
Model | Voltage | Frequency Range |
Digitax HD M75X 200 V |
200 V to 240 V ±10 % single phase | 45 to 66 Hz |
Digitax HD M75X 200 V |
200 V to 240 V ±10 % three phase* | 45 to 66 Hz |
Digitax HD M75X 400 V |
380 V to 480 V ±10 % three phase* |
45 to 66 Hz |
* Maximum supply imbalance: 2 % negative phase sequence (equivalent to 3 % voltage imbalance
between phases).